Linear Actuator Not Working? Troubleshooting and Testing Guide
Most linear actuator faults come from the power supply, the wiring or the switch, not the actuator itself. Work through these checks in order, starting with a direct test on a known-good 24VDC supply.
Step 1: Test the actuator directly
- Disconnect the actuator from the control box or switch.
- Connect its two motor wires straight to a known-good 24VDC supply (with a fuse) that can give the full-load current.
- It should move. Swap the two wires: it should move the other way.
- If it works here, the fault is in the switch, control box, remote or wiring, not the actuator.
Step 2: Match the symptom
| Symptom | Likely cause | What to do |
|---|---|---|
| No movement, no sound | No power, blown fuse, broken wire, or rod already at a limit | Measure voltage at the actuator plug; reverse polarity; check fuse and connectors |
| Moves only one way | One switch or relay contact not closing, or a limit switch is open | Test directly as in Step 1; check the switch wiring |
| Hums but does not move | Load above rating, supply too weak, or mechanism jammed | Check force with the force calculator; test unloaded; use a bigger supply |
| Runs slowly | Low voltage or voltage drop on long thin cables | Measure voltage at the actuator under load; use thicker cable |
| Stops after some cycles, works later | Overheating: duty cycle exceeded | Let it cool; keep within the 10% duty cycle |
| Two actuators move unevenly | Different loads; no synchronisation | Use a synchronising control box; read how to synchronise |
| Noisy or grinding | Side load on the rod, misalignment, or wear | Check both ends pivot freely and the load is guided |
Testing with a multimeter
- Supply voltage: set to DC volts; it should read about 24V at the actuator plug while switched on.
- Motor winding: with power off and the actuator mid-stroke, measure resistance across the two wires. A reading of a few ohms is normal; open circuit (no reading) points to a broken wire or motor fault.
- Current: measure the current while moving. Much higher than the datasheet value means overload or a mechanical problem.
Still not working?
Note the model, what you tested and the readings, and contact our technical team. Wiring help is in the wiring guide.
Frequently asked questions
Why does my linear actuator only move in one direction?
Usually a switch or relay contact is not closing in one direction, or the rod is resting on a limit switch. Test it directly on a 24VDC supply and swap the wires.
Why is my actuator humming but not moving?
The load is too high, the supply cannot give enough current, or the mechanism is jammed. Test it without load first.
How do I test a linear actuator?
Connect the two motor wires directly to a fused 24VDC supply. It should move, and reverse when you swap the wires.